Cisco Systems 6500-E Switch User Manual


 
RJ-21 Port Connector and Cabling Specifications
27
Cisco Communication Media Module for Catalyst 6500 Series Switch and Cisco 7600 Series Router Installation and Verification Note
RJ-21 Port Connector and Cabling Specifications
Caution Do not connect the WS-SVC-CMM-24FXS port adapter directly to a voicemail server, IVR application,
or fax server if the servers have unused wiring pairs with voltage on them. We recommend that you
connect the 25-pair cables to punch-down blocks and cross connect to the voicemail, IVR, or fax servers.
If you do not use punch-down blocks and cross connects to the WS-SVC-CMM-24FXS port adapter, you
could damage the port adapter. For example, the FLT-8 card for the Octel 250 uses every other pair for
its voice ports. The unused pairs have +36 VDC across ring-to-ground in an on-hook condition, and this
high voltage has been known to damage the WS-SVC-CMM-24FXS port adapter.
Use a standard RJ-21 Category 5 telco connector and cable to connect to the RJ-21 connector. Two types
of RJ-21 connectors are shown in Figure 15 and Figure 16. A pinout for the module’s RJ-21 connector
is provided in Table 7.
Figure 15 RJ-21 Telco Interface 90-Degree Cable Connector
Figure 16 RJ-21 Telco Interface 180-Degree Cable Connector
Warning
If the symbol of suitability with an overlaid cross appears above a port, you must not connect the
port to a public network that follows the European Union standards. Connecting the port to this type
of public network can cause severe personal injury or can damage the unit.
Statement 1031