Compaq 320 Server User Manual


 
2-4 AlphaServer GS80/160/320 Site Preparation
Table 2–3 gives the heat dissipation in minimally as well as fully configured
GS80 systems.
Table 2–3 Heat Dissipation in GS80 Systems
System Configuration Heat Dissipation
GS80, one drawer
Minimal configuration:
Two power supplies, one CPU module, one memory
module, one system I/O module, minimally
configured PCI, one disk drive
1,150 W/3,800 Btu/hr
GS80, two drawers
Minimal configuration:
Four power supplies, one CPU module, one memory
module, one system I/O module, minimally
configured PCI, one disk drive
1,900 W/6,400 Btu/hr
GS80, one drawer
Full configuration:
Three power supplies, four CPU modules, four
memory modules, two system I/O modules, one PCI
box, one storage shelf with six disk drives
2,100 W/7,150 Btu/hr
GS80, two drawers
Full configuration:
Six power supplies, eight CPU modules, eight
memory modules, four system I/O modules, one PCI
box, one storage shelf with six disk drives
3,450 W/11,650 Btu/hr
See Table 2–9 for the power specifications of the I/O expander cabinet.