Dell H967N Power Supply User Manual


 
43
Operation
|
Table 7. Settings (continued)
Description Default SettingAvailable Settings
Battery Saving Mode [Disabled] [10%] [20%] [30%]...[100%]
The UPS output is turned off in five minutes if the
UPS is on battery and output power is below the
selected level.
Disabled
On Battery Notice Delay [0] [1s] [2s]...[99s]
The UPS issues a “UPS on battery” notice in the
specified number of seconds after the UPS starts to
discharge the batteries.
0s
Site Wiring Fault Alarm [Enabled] [Disabled] Enabled for low
voltage models;
Disabled for all other
models
Bypass Voltage Low Limit [-6%] [-7%]...[-20%] of nominal
The Bypass operation is disabled if the measured
bypass voltage level is below the nominal output
voltage (-15%).
NOTE: The Qualify Bypass setting may overrule the
Bypass Voltage Low Limit setting.
-15% of nominal
Bypass Voltage High Limit [+6%] [+7%]...[+20%] of nominal
The Bypass operation is disabled if the measured
bypass voltage level is above the nominal output
voltage (+10%).
NOTE: The Qualify Bypass setting may overrule the
Bypass Voltage High Limit setting.
+10% of nominal