Delta DVPEN01-SL Switch User Manual


 
Ethernet Communication Module DVPEN01-SL
DVP-PLC Operation Manual
25
E-Mail will be sent to the designated recipients when the E-Mail is triggered. To trigger E-Mail, set
the value is CR#3 ~ CR#6 as “1”.
6. See “Application Examples Section 6.8” for more details.
Notes:
To correctly send out E-Mails, there has to be a SMTP server in the network. When we send out
an E-Mail, the mail will be sent to SMTP server first, and the server will further send the mail to the
designated address.
5.5 Data Exchange
DVPEN01-SL is able to designate a data exchange area for PLC MPUs to exchange and synchronize their
data.
Setting up DVPEN01-SL data exchange
1. Enable Data Exchange:
Check the box to enable or disable data exchange. Start data exchange after enable it.
2. Execute Mode:
You can set it to ”Always Enable” or ”Program Control”. When set to “Always Enable”,
DVPEN01-SL will execute data exchange continuously until the setting in DCISoft is changed.
When set to “Program Control”, DVPEN01-SL will execute data exchange according to the
program setting (CR#13 = 2: Execute; CR#13 = 0: Stop).
3. Communication Address & Data exchange host IP:
You have to enter the IP address of DVPEN01-SL at the other end. For example, if you would
like DVPEN01-SL to exchange data with 192.168.0.1, set No. 1 as 192.168.0.1. When the data
are being exchanged, if the value in CR#28 is H’0001, the data will be exchanged with
192.168.0.1.
4. Master Address & Slave address & Quantity.
Read (Å): Start address of the master’s receiving register Å Start address of the slave’s
sending register
Write (Æ): Start address of the master’s sending register Æ Start address of the slave’s