3.4 PID PROG
Press for 3 seconds in the main screen to enter the “initial setting mode”. Press several
times until the parameter is displayed.
Display Explanations
PV SV Status of the temperature controller
The control modes include: ON/OFF, MANUAL, PID and PID
PROG. Default = PID. Select “PID PROG” here.
DTB offers 8 patterns and 8 steps for each pattern, totaling 64
steps. Range of a pattern: OFF ~ 7. OFF = the function disabled.
Temperature SV for pattern 0 and step 0
Time SV for pattern 0 and step 0
Temperature SV for pattern 0 and step 1
Time SV for pattern 0 and step 1
… …
… …
Temperature SV for pattern 0 and step 7
Time SV for pattern 0 and step 7
Actual number of steps executed in pattern 0
Actual number of loops executed in pattern 0
Pattern linked after the execution of pattern 0 is completed.
OFF = end of linking patterns
Return to
Back to
top
Press to return to the main screen.
Return to the main screen to switch to the functions below.