Eaton Electrical 1000 Network Card User Manual


 
MODBUS REGISTERS
EATON Power Xpert
®
Gateway Series 1000 Card User’s Guide S 164201670 Rev 1
54
PDU/RPP Registers and Alarms
This section contains information for the PDU/RPP Registers (FC 04) and
PDU/RPP Alarms (FC 02).
PDU/RPP Registers (FC 04)
To read the vendor name in the PDU/RPP, set the Modbus program to
Unit ID 1 and register 1001:
IP: <IP address of PDU/RPP>
Unit ID: 1
Starting Register: 1001
Number of registers: 32
Function Code: 04
The PDU/RPP returns 32 registers containing up to 64 characters. There
are two ASCII characters per register, so the vendor name could be
displayed as POWERWARE.
Table 3. PDU/RPP Registers (FC 04)
Name Register Data Type Bytes
Vendor Name 1001 STRING 64
Model Name 1033 STRING 64
Display Name 1065 STRING 64
Device Type 1097 UINT 4
Device ID 1099 UINT 4
Device Guid 1103 STRING 40
Serial Number 1123 STRING 64
Conn Style 1159 UINT 2
Device Comm Address 1160 STRING 64
Device Baud Rate 1192 UINT 4
Time Sync Period 1194 UINT 4
Data Update Period 1196 UINT 4
Device VAR Rating 1198 UINT 4
Device Volts In Rating 1204 UINT 4
Device Volts Out Rating 1206 UINT 4