Eaton Electrical QSNAP Network Card User Manual


 
Intelligent Technologies (IT.) QSNAP
8
Pub. No. MN05001001E
February 2002
Operation
This section provides details about the following features and aspects of QSNAP operation:
Out of box operation
Typical application
Enhanced features
Input/output data
Status LED
Truth table
“Out of Box” Operation
When the QSNAP is properly installed and has a properly congured Group ID, as per the
Installation section, the following default data lists will be presented to the system for use
by a gateway.
For further information on the meaning of the terms in the assemblies, see the Enhanced
Features section on Page 10.
Table 6: Default Input Data from QSNAP
Table 7: Default Output Data to QSNAP
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
3-Phase Average RMS Current LSB Byte 0
3-Phase Average RMS Current Byte 1
3-Phase Average RMS Current Byte 2
3-Phase Average RMS Current MSB Byte 3
% Thermal Capacity LSB Byte 4
% Thermal Capacity MSB Byte 5
Fault/Warning Codes LSB Byte 6
Fault/Warning Codes MSB Byte 7
Reserved Warning Faulted Local
Control
Resetting Permissive Running
2
Running
1
Byte 8
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved Reserved Local
Control
Local/
Remote
Fault
Reset
Permissive Run 2 Run 1 Byte 8