Emerson 000-VA Power Supply User Manual


 
Specifications
Liebert
®
GXT3
36
Relative Humidity 0-95% non-condensing
Operating Elevation Up to 1000m (3281 ft) at 25°C (77°F) without derating
Audible Noise <55 dBA, at 1 meter from the rear <50 dBA, at 1 meter from the front or sides
Agency
Safety IEC62040-1:2008 version, GS mark
EMI/EMC/C-Tick EMC IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6)
ESD IEC/EN EN61000-4-2, Level 4, Criteria A
Radiated Susceptibility IEC/EN EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient IEC/EN EN61000-4-4, Level 4, Criteria A
Surge Immunity IEC/EN EN61000-4-5, Level 3, Criteria A
Transportation ISTA Procedure 1A
Table 8 Operating temperature parameters
Ambient Temperature, °C (°F)
pf @30°C ±3°C
(pf @ 86°F ±5.4°F)
pf @40°C ±3°C
(pf @ 104°F ±5.4°F)
5000RT230, 6000RT230 0.8pf 0.8pf
10000RT230 0.9pf 0.8pf
Table 9 Power distribution specifications
Model Number
PD2-CE6HDWRMBS PD2-CE10HDWRMBS
Amp Rating 32 Amps 63 Amps
Input Power Connection Single-phase (L-N-G) hard-wired, 6-10mm
2
(8-10AWG)
Output Power Connection Single-phase (L-N-G) hard-wired, 6-10mm
2
(8-10AWG)
Includes:
Two IEC320 C19 16A/250V Sockets
Six C13 10A/250V Sockets
Manual Bypass Switch with Indicator Lamps
Four IEC320 C19 16A/250V Sockets,
Four C13 10A/250V Sockets
Manual Bypass Switch with Indicator Lamps
Input Branch Circuit
Breaker, Supplied by User
32A 63A
Table 7 UPS specifications (continued)
Model # GXT3-5000RT230 GXT3-6000RT230 GXT3-10000RT230