Specifications
35
9.0 SPECIFICATIONS
Table 11 Specifications of GXT3-500RT120 - GXT3-1000RT120 and GXT3-1000MT120 UPS
Parameters
Product Model
GXT3-500RT120
(500VA/450W)
GXT3-700RT120
(700VA/630W)
GXT3-1000RT120
(1000VA/900W)
GXT3-1000MT120
(1000VA/900W)
Dimensions, D × W × H, in. (mm)
Unit
19.7 x 16.9 x 3.4
(497 × 430 × 85)
15.4 x 6.9 x 8.9
(390 × 175 × 225)
Shipping
25.5 x 23.9 x 10.6
(647 x 607 x 270)
22.1 x 12.9 x 14
(562 × 327 × 355)
Weight, lb (kg)
Unit 37 (16.8) 37.5 (17)
Shipping 44.1 (20) 36 (16.5)
Input AC
Voltage Range (typical) 120VAC nominal; variable based on output load
90% ~ 100% loading 90VAC/140VAC
70% ~ 90% loading 86VAC/140VAC
30% ~ 70% loading 77VAC/140VAC
0 ~ 30% loading 60VAC/140VAC
Frequency 40Hz ~ 70Hz; Auto Sensing
Input Power Cord 10 ft. attached w/ NEMA 5-15P plug
Output AC
Output Receptacles 5-15R × 6
Voltage 110/115/120VAC (user-configurable); ±3%
Waveform Sine wave
Utility (AC) Mode Overload 200% for 2 seconds; 150% for 50 seconds with transfer to bypass
Battery
Type Valve-regulated, nonspillable, lead acid
Qty × V× Rating 4 × 12V × 5.0Ah
Battery Mfr./Part # YUASA/NPH5-12; CSB/ HR 1221W; CSB/GP1245
Backup Time See Table 15
Recharge Time
3 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown
(Internal Batteries Only)
Environmental Requirements
Operating Temperature, °F (°C) 32 to 104 (0 to 40); see Table 14 - Operating temperature parameters
Storage Temperature, °F (°C) 5ºF to 122ºF (-15ºC to 50ºC)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation
Up to 10,000 ft. (3000m) at 77ºF (25ºC) without derating
Storage Elevation 50,000 ft. (15000m) maximum
Audible Noise
<43dBA max @ 3ft. (1m) front and sides
<46dBA max @ 3ft. (1m) rear
< 50 dBA, at 3ft. (1m) rear
< 45 dBA, at 3ft. (1m) front and sides
Agency
Safety UL 1778, cUL Listed
RFI/EMI FCC Part 15, Class A=CISPR22 Class B
Surge Immunity IEC 62040-2 2nd Ed
Transportation ISTA Procedure 1A