Emerson 240V Power Supply User Manual


 
Operating Instructions
26
Bypass Alarm Mode: Allows the user to enable/dis-
able alarm, indicating that the bypass is not quali-
fied.
Intelli-Battery Ca.: Allows the user to enter the
quantity of intelligent battery cabinets installed.
Air Filter Reminder: Allows the user to set a warn-
ing reminder to check the air filters.
Guarantee Shutdown: Allows the user to guarantee
a shutdown after a low battery warning is announced,
even if the utility becomes qualified.
Line Compensation: Allows the user to control the
amount of line drop compensation to be applied to the
nominal output voltage. Line drop compensation is
intended to compensate for any IR drop that may
occur when the UPS is a significant distance from the
protected load.
Factory Defaults: Allows the user to reset all set-
tings to the values in effect when the UPS was
shipped from the factory.
Bypass Alarm Mode
> Enable
Disable
Enter Intelli-
Battery cabinet
count
x
Air Filter Reminder
2 weeks
4 weeks
10 weeks
26 weeks
52 weeks
* Disable
Guarantee Shutdown
Enable
* Disable
Output Volt: x
Increase Decrease
ESC to cancel
to Accept & Exit
Load Factory Default
Are you sure?
Press for yes
Press ESC for no