Emerson 300 Switch User Manual


 
ADJUSTMENTS
(continued)
4 --- 2
Do not make any setting changes
while the controller is energized.
How to Change a Setting
1. Prev ent the transfer switch from operating by discon-
nec ting one sourc e first, then the other, as follo w s:
a. If the transfer switch is in the Normal position,
open the emergency source circuit breaker.
Turn the engine starting control to off.Then
open the normal source circuit breaker.
b. If the transfer switch is in the Emergency
position, open the normal source circuit breaker.
Tu rn engine starting control to test or run.Then
open the emergency source circuit breaker.
2. Disconnect both harness plugs from controller by
squeezing the latches. Do not pull on the wires.
3. Remove cover from the controller by releasing latch
on rig h t side with your thum b . See Figu r e 4 - 1.
4. Locate the appropr iate adjustm ent potentiom eter or
DIP switc h for the setting that you want to chan g e.
Refer to Table 4-1 and Table 4–2 on page 4-1 and
Figure 4-2, Figure 4–3, Figure 4–4 on page 4–2.
5. Use a small screwdriver to turn the potentiometer
clockwise to increase the t ime delay or counter-
clockwisetodecreaseit. SeeFigure4-3.
6. Use a bal l - p oin t pen (or similar pointed tool) to sl ide
the switch actuators left or righ t so they match the
ill u str ation next to the setting (l eft = off, right =
on). Rec heck the setting. See Figure 4-4.
7. Install the cover on the controller by hooking it on
the left si de and latching the right side.
8. Reconnect both harness plugs to the controller by
aligning and pressing straight in until latches click.
Close the enclosure door.
9. Cl ose the enclosure door, then restore both sources:
a. If the transfer switch is in the Norm al position
first close the normal source circuit breaker, then
cl ose the emergenc y sourc e circu it breaker.
b. If the transfer switch is in the Emergency
position, close the normal source circuit
breaker. Theloadwillbeautomatically
retransferred to the normal source. Then close
the emergency source circuit breaker.
10. Turn the engine starting control to automatic.
thumb
latch
cover
hook on
left side
Figure 4-1. Controller cover latch.
9volt
alkaline
battery
battery
on/off
jumper
retransfer
to normal
time delay
transfer to
emergency
time delay
harness
plugs
S3 DIP
switch
S1 DIP
switch
S2 DIP
switch
P1
P2
J5
Figure 4-2. Location of potentiometers.
P1 or P2
potentiometer
clockwise to
increase
counterclockwise
to decrease
Figure 4-3. Changing time delay potentiometers.
DIP
switches
SW1
SW2
SW3
actuator
onoff
(8 on each DIP switch)
Figure 4-4. Setting DIP switch actuators.