Battery Installation
44
Figure 27 Multiple temperature sensors, battery circuit breaker box and UPS module
NOTE:
1. Each probe consists one OT6-4 terminal and one precision temperature sensor that is
sealed in the OT6-4's terminal. The whole probe is supplied as one cable.
2. The type of temperature transport board illustrated in Figure 27 is TMP-2.
3. The signal cables in the Figure 27 must be shielded and double insulated.
4. The temperature monitoring cable must be less than 10m while the signal transmission
distance of the transport board must be less than 100m.
Temperature
Sensor
TMP-2
+
IN
-
NC
12V
GND
OUT
BCB Box
BCB Control
Board – C2
+12V
GND
OUT
X103
X105
X104
X106
X108
UPS
Monitor
Board
– U2
X7
-12V
GND
BAT-T
Temperature
Sensor
TMP-2
+
IN
-
NC
12V
GND
OUT
Temperature
Sensor
TMP-2
+
IN
-
NC
12V
GND
OUT
Temperature
Sensor
TMP-2
+
IN
-
NC
12V
GND
OUT
Type: W3 L = 5m Type: W3 L = 30m
Cable W3 (L=5m) is packed with the temperature sensor.
Cable W3 (L=30m) is packed with the BCB box.