Wiring Connections
27
6. The UPS System Control Cabinet (SCC) neutral must be connected to one common point and
solidly grounded per requirements of the National Electrical Code. The ground connection inside
the UPS SCC/switchgear cabinet may be required by the power wiring configuration at your site.
7. For battery systems: DC power cables (and ground) from battery to UPS module and between
battery cabinets/strings. Observe polarity. When multiple conduits are used, an equal number of
positive and negative cables should be contained in each conduit.
8. For remote battery: Install DC power cables (and ground) from battery to Module Battery
Disconnect, and then to UPS Module DC bus. Observe polarity.
9. Module Battery Disconnect control wiring to UPS module and between battery cabinets, if
applicable. Wiring must be run in individual separate steel conduit.
10. Control wiring from System Control Cabinet (SCC) to UPS modules. Wiring must be run in
individual separate steel conduit. Refer to Figures 30, 31 and 38 through 42 or your submittal
drawings.
11. Control connections between the System Control Cabinet (SCC) and the Maintenance Bypass
panelboard or switchgear. Refer to your submittal drawings.
12. Control wiring to the optional Remote Monitor Panel, if used. Selected alarm messages are also
available for customer use through a set of contacts on an optional separate terminal board.
Wiring must be run in individual separate steel conduit.
13. Emergency Power Off control wiring (to SCC) must be run in separate steel conduit.
14. Optional communications wiring (to SCC) for terminals, site monitoring or modem must be run in
separate steel conduit.
15. Any additional special wiring required at your site. Refer to Figures 29 through 42 or your
submittal drawings.
!
CAUTION
UPS bypass and system output neutral must be connected to only one common point in the
UPS system. This neutral line must be grounded at the source. Refer to 6.0 - Configuring
Your Neutral and Ground Connections for further details.
NOTE
DC power and battery circuit breaker control cables are provided with Liebert battery cabinets
for use between multiple cabinets when bolted together. Power cables are sized for
interconnecting battery cabinets. Battery cabinets specified for bolting up to the UPS are
shipped with power cables to connect the battery cabinet system to the UPS module. Field-
supplied cabling must be provided to connect stand-alone battery cabinets to the UPS module.
Connections from the final battery cabinet to the UPS are provided in the field.
!
WARNING
Do not make any connections between battery tiers in the battery cabinet. These connections
will be made by the Liebert Global Services representative during start-up.
!
CAUTION
Cables between batteries and the UPS should be run in matched pairs,
positive-with-negative, within each conduit or cable run. Grouping
like-polarity cables together (i.e., positive-with-positive and
negative-with-negative) can cause stress or damage to the cables,
conduit or buswork.