Emerson 7000 Switch User Manual


 
Voltage and Frequency Sensing
3-Phase under and over voltage settings on normal
and emergency sources.
Under and over frequency settings on normal and
emergency.
True RMS Voltage Sensing with +/- 1% accuracy;
Frequency Sensing Accuracy is +/- 0.2%.
Selectable settings: single or three phase voltage
sensing on normal and emergency; 50 or 60Hz.
Phase sequence sensing for phase sensitive loads.
Voltage unbalance detection between phases.
Status and Control Features
Output contact (N/O or N/C) for engine-start signals.
Selection between “commit/no-commit” on transfer
to emergency after engine start and normal restores
before transfer.
Advanced inphase algorithm which automatically
measures the frequency difference between the two sources
and initiates transfer at appropriate phase angles to
minimize disturbances when transferring motor loads.
Event log displays 99 logged events with the time and
date of the event, event type and event reason.
Output signals for remote indication of normal and
emergency source acceptability
Statistical ATS/System monitoring data screens which provide:
Total number of ATS transfers.
Number of ATS transfers caused by power source failure.
Total number of days ATS has been in operation.
Total number of hours that the normal and emergency
sources have been available.
Time Delays
Engine start time delay - delays engine starting signal to
override momentary normal source outages - adjustable
0 to 6 seconds.
Transfer to emergency time delay - adjustable 0 to 60
minutes.
Emergency source stabilization time delay to ignore
momentary transients during initial generator set
loading - adjustable 0 to 6 seconds.
Retransfer to normal time delay with two settings:
Power failure mode - 0 to 60 minutes.
Test mode - 0 to 60 minutes.
Unloaded running time delay for engine cooldown -
adjustable 0 to 60 minutes.
Pre and post transfer signal time delay for selective
load disconnect with a programmable bypass on source
failures - adjustable 0 to 5 minutes. This signal can be
used to drive a customer furnished relay, or for (2) sets
of double throw contacts rated 3 amps at 480 volts AC,
specify ASCO optional accessory 31Z.
Fully programmable engine exerciser with seven
independent routines to exercise the engine generator,
with or without loads, on a daily, weekly, bi-weekly or
monthly basis.
Contains all alarm signals, logic and time delays for
use with closed transition switches.
Insynch time delay - 0 to 3 seconds.
Failure to synchronize - 1 to 5 minutes.
Extended parallel - 0.1 to 1.0 seconds.
Delayed transition load disconnect time delay -
adjustable 0 to 5 minutes.
Page 11
7000 Series Microprocessor Controller
Features
Digital microprocessor.
Touch pad programming of features and settings
without the need for meters, or variable power supplies.
Sixteen (16) selectable operating voltages available in
a single Controller.
On-board diagnostics provide control panel and ATS
status information to analyze system performance.
Displays and counts down active timing functions.
Selectable multi-language display
(English, German, Portuguese, Spanish, or French.
For others contact ASCO).
Password protection to prevent unauthorized tampering
of settings.
Serial communications board (RS-485 protocol)
for remote monitoring and control with ASCO
PowerQuest
®
and SiteWeb™ communications
products. Specify optional accessory 72A.
Load shed option for SYNCHROPOWER® bus
optimization applications. Specify optional accessory 30B.
ASCO