Emerson GXT3 230V Power Supply User Manual


 
Specifications
34
12.0 SPECIFICATIONS
Table 7 UPS specifications
Model # Liebert
®
GXT3
5000RT230U
Rating 5000VA/4000W
Dimensions, mm (in)
Unit, W x D x H 570 x 430 x 220 (22.4 x 16.9 x 8.7)
Shipping, W x D x H 745 x 530 x 516 (29.3 x 20.9 x 20.3)
Weight, kg (lb)
Unit 60 (132.2)
Shipping 71 (156.5)
Input AC Parameters
Operating Frequency, Nom 50 or 60Hz (Factory Default = 50)
Factory Default VAC 230VAC
User-Configurable VAC
220/230/240VAC
(May be modified using included configuration program)
Operating Voltage Range Without Battery Operation 176 - 280VAC
Maximum Allowable VAC 280VAC
Input Frequency Without Battery Operation 40 - 70Hz
Input Power Connection
Hardwire Terminal Block Standard
(See 3.3 - Removable Power Distribution Box)
Output AC Parameters
Factory Default VAC
230VAC
Output Connections
Hardwire Terminal Block Standard
(See 3.3 - Removable Power Distribution Box)
Frequency 50Hz or 60Hz, Nominal
Waveform Sinewave
Main Mode Overload
>200% for 5 cycles; 151 - 200% for 1 seconds; 131-150% 10
seconds; 105 - 130% 1 minute
Battery Parameters
Type Valve-regulated, non-spillable, lead acid
Quantity x V 20 x 12V
Battery Mfr. / Part # 5AH battery, CSB HR1221W or YUASA NPH5-12
Backup Time
See Table 11 - Typical battery run times, minutes at 25°C
(77°F ), 100% resistive load and
Recharge Time (Internal Batteries) 3 hr. to 90% capacity after full discharge into 100% load
Bypass Protection Limits
Disable Bypass Operation If input voltage exceeds ±15% of the nominal voltage
Re-Enable Bypass Operation
If input voltage returns to within ±10% of nominal output
voltage
Disable Bypass operation When the input frequency prevents synchronous operation
Environmental
Operating Temperature, °C (°F)
0 to 40 (32 to 104) see Table 8 - Operating temperature
parameters
Storage Temperature, °C (°F) -15 to 50 (5 to 122)
Relative Humidity 0-95% non-condensing
Operating Elevation Up to 1000m (3281 ft) at 25°C (77°F) without derating
Audible Noise
<55 dBA at 1 meter from the rear;
<50 dBA, at 1 meter from the front or sides