Emerson GXT3 230V Power Supply User Manual


 
Specifications
35
Agency
Safety IEC62040-1:2008 version; UL 1778, c-UL Listed
EMI/EMC IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6); FCC Class A
ESD EN61000-4-2, Level 4, Criteria A
Radiated Susceptibility EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient EN61000-4-4, Level 4, Criteria A
Surge Immunity EN61000-4-5, Level 3, Criteria A
Transportation ISTA Procedure 1A
Table 8 Operating temperature parameters
Ambient Temperature, °C (°F)
pf @30°C ±3°C
(pf @ 86°F ±5.4°F)
pf @40°C ±3°C
(pf @ 104°F ±5.4°F)
5000RT230U 0.8pf 0.8pf
Table 9 Power distribution specifications
Model Number
PD2-CE5HDWRMBSU
PD2-Amp Rating 32 Amps
Input Power Connection 3-Wire Hard-Wired, 6-10mm
2
(8-10AWG)
Output Power Connection 3-Wire Hard-Wired, 6-10mm
2
(8-10AWG)
Input Branch Circuit Breaker Supplied by User 32A
Table 10 External battery cabinet specifications
Model Number
Liebert
®
GXT3
-240VBATTCE
Used with UPS Model
Liebert GXT3 5000RT230U
Dimensions, W x D x H, mm (in.)
Unit (with bezel) 570 x 430 x 148 (22.4 x 16.9 x 5.8)
Shipping 745 x 530 x 407 (29.3 x 20.8 x 16)
Weight, kg (lb)
Unit 50.4 (111)
Shipping 54 (119)
Battery Parameters
Type Valve-regulated, non-spillable, lead acid
Quantity x V 1 x 20 x 12V
Battery Manufacturer, Part # 5AH battery - CSB HR1221W or YUASA NPH5-12
Backup Time See
Table 11
Environmental
Operating Temp, °C (°F)
0 to 40 (32 to 104)
see Table 8 - Operating temperature parameters
Storage Temp , °C (°F) -15 to 50 (5 to 122)
Relative Humidity 0-95% non-condensing
Operating Elevation Up to 1000m (3280.83 ft.) at 25°C (77°F)
Agency
Safety IEC62040-1:2008 version
Transportation ISTA Procedure 1A
Table 7 UPS specifications (continued)
Model # Liebert
®
GXT3
5000RT230U