Emerson Surge and Signal Protection Surge Protector User Manual


 
Emerson Network Power.
The global leader in enabling Business-Critical Continuity.
EmersonNetworkPower.com
AC Power Systems
Connectivity
DC Power Systems
Embedded Power
Integrated Cabinet Solutions
Outside Plant
Power Switching & Controls
Precision Cooling
Site Monitoring
Surge & Signal Protection
Services
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, Ohio 43229
800 877 9222 Phone (U.S. &
Canada Onl
y)
614 888 0246 Phone (Outside U.S.)
614 841 6022
FAX
Via
Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
Italy
39 049 9719 111 Phone
39 049 5841 257 FAX
Emerson Network Power Asia Pacific
7/F., Dah Sing Financial Centre
108 Gloucester Rd, Wanchai
Hong Kong
852 25722201 Phone
852 28029250 FAX
liebert.com
Technical Support
800 288 6169 Toll-Free
607 724 2484 Phone
607 722 8713 Fax
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2005 Emerson Electric Co.
Specifications
While every precaution has been taken to ensure accuracy and
c
om
pleteness in this literature, Liebert Corporation assumes no
responsibility, and disclaims all liability for damages resulting
from use of this information or for any errors or omissions.
© 2005 Liebert Corporation. All rights reserved throughout
the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks
of their respective owners.
® Li
ebert and the Liebert logo are registered trademarks
o
f the Li
e
be
r
t C
or
por
a
tion.
SL-22060 (R3/06) Printed in USA
Connection Means Parallel Connected
A
gency Listing UL 1449 Listed (Second Edition), UL 1283, CUL
Protection Modes All modes standard (L-N, L-G, N-G, L-L); Optional – any combination
Surge Current Capacity 250 to 750kAmps per phase depending on model
Pr
imary Stage Joule H1 Models – 250 Joules
R
ating (L-N) per phase H2 Models – 500 Joules
EMI/RFI Filtering 41 dB at 100 KHz, 31 dB at 1 MHz, 35 dB at 10 MHz, 53 dB at 100 MHz
Response Time Picosecond range
R
epetitive Surge 15,000 - 120,000 10kA Category C3 surges per phase depending on model
Enclosure NEMA 12 standard Optional - NEMA 3R, 4, 4X and caseless
Line Frequency 47-63 Hertz
Line Voltage +/-15% nominal
Temperature -40 to +60 degrees C
Relative Humidity 0 to 95% noncondensing
Altitude 0 to 18,000 feet
Audible noise Less than 45 dBa
Warranty 10-years parts, 5-year labor
Standard Features Unit status indicators, Dual, isolated form C dry contacts
Optional Features Integral disconnect, Audible alarm, Transient counter – single or dual