ETA-ECM20, ETA-ECM20M SPECIFICATIONS
General
Type: Power Conditioner Suppressor Module
Power Requirements: 120V 60Hz
Power Consumption: .5W
RoHS Compliant: Yes
Safety Approval: MET (UL 1449 Code)
Panel
Switched Outlets: Two, 20A
Spike&SurgeSuppression: H-N,N-G,H-G
Manual Override: Slide switch
ExtremeVoltageShutdown: ETA-ECM20MModelonly,(EVS)Below102VorAbove
132V AC Line (When Used With ETA-ECS6RM)
Connectors: 5PositionPhoenixEuroBlockStyle
FuseProtection: 20ASlowBlow
DCVRemoteTrigger: 5–24DCV
Remote Trigger: SPST Contact
StatusSignals: OutputforVoltageandCurrentData
(ETA-ECM20M model only)
Indicators: Incoming AC, Active, AC Fault (ETA-ECM20M model only)
AC Mains Interconnect: Screw terminal block
Technical Data:
Current Rating: 15 amps
Operating Voltage: 102 - 132 VAC
High Voltage Surge Protection: Trigger at 133 VAC, 1ms typically
(When Used With ETA-ECS6RM) (ETA-ECM20M model only)
Spike&SurgeSuppression: H-N,N-G,H-G
Low Voltage Protection: Trigger 101 VAC, 1ms typically
(When Used With ETA-ECS6RM) (ETA-ECM20M model only)
Spike Protection Modes: Circuitry on incoming AC Mains.
Minimum Spike Clamping Voltage: 460 VRMS @ 3,000 amps
Maximum Spike Clamping Voltage: 6000V
Maximum Spike Clamping Response Time: 1 nanosecond
Spike Clamping Voltage @ 100A: 1250Vp for 20µs
Maximum surge current: 6,500 amps
Energy Rating @ 2ms: 600 Joules
NoiseAttenuationEMI/RFISequencer: 10dB@10kHz,40dB@100kHz,100dB@10MHz
(ETA-ECM20M model only)
Temperature Range: 5º to 35º C
Humidity Range: 5% to 95% R.H.
Mechanical:
ChassisFinish: Black
Mounting: #8 5/16” self tapping screws
Dimensions: 3.0"Hx8.5"Lx3.5"W(7.6cmx21.6cmx8.9cm)
Unit Weight: ETA-ECM20=1.25 lbs(.68 kg), ETA-ECM20M=1.75 lbs(.80 kg)
©2009 ETA Systems All rights reserved. ETA003568 RevA 05/09
ETA-ECM20 & ETA-ECM20M
Electrical Control Module 20A Power Conditioner