Falcon FN6KRM-2 Power Supply User Manual


 
6.2 How to start up the UPS without utility power present (Cold Start)
1. Press the “On” button for 6 seconds to awaken the UPS. The UPS will beep twice and
display G below. Immediately upon G being displayed, press the “On” button for another 6
seconds. The UPS will beep twice again and sequence through H and I.
After depressing the “On” button
for 6 seconds the first time, the
UPS will beep twice and “OFF”
or “BPS” will be displayed.
After depressing the “On” button
the second time for 6 seconds,
the UPS will display input
voltage H and I. The UPS output
voltage will be present and the
UPS will continue to run on
battery until the batteries are
discharged or the “Off” button is
pressed for 3 seconds.
21
6.3 How to turn off the UPS inverter and place the UPS into bypass mode
1. While the UPS is operating in utility, inverter or battery mode, depress the “Off” button until the UPS
sounds two audible beeps. The UPS will switch to static bypass and turn off the inverter. The LCD
will display “OFF” or “BPS”. The connected load will now be powered directly from the utility source.
The UPS will continue to operate in bypass mode until:
a. The “On” button is depressed for three seconds, which will return the UPS to normal
inverter mode operation.
b. The UPS and Bypass Input circuit breakers are turned off, which will shut down the UPS and
the connected load completely.
6.4 How to completely shutdown the UPS
1. While the UPS is operating in utility, inverter or battery mode, depress the “Off” button until the UPS
sounds two audible beeps. The UPS will switch to static bypass and turn off the inverter. The LCD
will display “OFF” or “BPS”.
2. Turn off the UPS and Bypass input circuit breakers, which will shutdown the UPS and the
connected load completely.
Note, the UPS may continue to run for 30 seconds to one minute prior to turning off.