Appendix B. Driver Notes
Appendix B.1. Setting the FieldServer’s DeviceNet MAC ID and Baudrate
The MAC ID and Baudrate can be set in the FieldServer’s CSV file using the
System_Station_Address and DNet_Master_Baudrate parameters or it can be set with DIP switches
as depicted below.
Note:
The System_Station_Address parameter must be removed from the configuration file if the DIP
switch setting is to be used.
If System_Station_Address has not been defined in the CSV file, the DIP switch value for both MacID
and Baudrate will be used and the baud parameter in the CSV file will be ignored.
Appendix B.2. Using the Command and Status Data Arrays
The Command Data Array controls the Scanner’s mode which can be either Run or Idle. The Scanner
can only be configured when in Idle mode. A non-zero value at offset zero in the Command Data
Array will place the Scanner in Run mode; a value of zero will place it in Idle mode. The Scanner