3. Hardware Connections
The FieldServer is connected to the DeviceNet network as shown in the connection drawing below.
Connector Pinouts
Pin
Signal Description Wire color
1 V- Negative supply voltage
black
2 CAN_L CAN_L Bus line blue
3 SHIELD
Cable Shield (bare)
4 CAN_H
CAN_H Bus line white
5 V+ Positive Supply Voltage red
3.1. Hardware Connection Tips / Hints
Use the recommended network cable and terminators as specified by the DeviceNet network
organization and/or the manufacturer of your network equipment.
Terminate each end of the DeviceNet network with a 121 Ω resistor
The bus interface shall be supplied with 24DC ± 10% on the Fieldbus connector