FS-8700-16 BACnet PTP Serial Driver Manual Page 4 of 20
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: 888-509-1970 email: support@fieldserver.com
3. Hardware Connections
It is possible to connect a BACnet device to any of the eight RS-232
3
ports. These ports just need to be
configured for BACnet in the configuration file.
Configure the PLC (or BCU) according to manufacturer’s instructions
RJ45 to
EIA232
Connector
RJ45 Connector
FUNCTION FROM TO COLOUR
Rx RJ45-01 DB9F-03 WHITE
GND RJ45-04 DB9F-05 GREEN
Tx RJ45-08 DB9F-02 BLUE
DB9M
FUNCTION FROM TO COLOUR
RX RJ45-01 DB9M-02 GREY
CTS RJ45-02 DB9M08 BROWN
DSR RJ45-03 DB9M-06 YELLOW
GND RJ45-04 DB9M-05 GREEN
GND RJ45-05 RED
TX RJ45-08 DB9M-03 BLUE
RTS RJ45-07 DB9M-07 ORANGE
DTR RJ45-06 DB9M-04 BLACK
8917-03 WIRE LIST
BASE NAME:
FILE NAME:
FIELDSERVER
BACNET PTP
CONNECTION DIAGRAM
DATE: 7/30/
06
BY: MC
(408)-262-2299
DB9F
8917-02 WIRE LIST
Note that connection to a Trane BCU requires the 8917-02 option.
3
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.