FS-8700-16 BACnet PTP Serial Driver Manual Page 6 of 20
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: 888-509-1970 email: support@fieldserver.com
Example
// FieldServer
FieldServer
Title, System_Node_ID, Network_Number
BACnet_PTP, 11, 2
4.3. Client Side Connection Descriptions
Section Title
Connections
Column
Title
Function Legal Values
Port Port Name P1-P8
4
Baud* Specify baud rate
110; 300; 600; 1200; 2400; 4800; 9600; 19200; 38400;
57600; 115000
Parity* Specify parity
Odd, Even, None
Data_Bits* Specify data bits
7, 8
Stop_Bits* Specify stop bits
1,2
Protocol
Specify Protocol
Used
BACnet_PTP
Example
// Client Side Connections
Connections
Port, Baud, Parity, Data_Bits, Stop_Bits, Protocol
P8
,
9600, Even, 7, 1, BACnet_PTP
4.4. Client Side Node Descriptors
Section Title
Nodes
Column Title Function Legal Values
Node_Name Provide name for node Up to 32 alphanumeric characters
Node_ID Node ID of physical server node (the BCU) 1 - 4194303
Protocol Specify protocol used BACnet_PTP
Port Specify port P1-P8
5
Example
// Client Side Nodes
Nodes
Node_Name, Node_ID, Protocol, Port
BCU_1, 1, BACnet_PTP, P8
4
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.
5
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.