FieldServer FS-8700-60 Computer Drive User Manual


 
FS-8700-60 Gardner Denver Manual Page 5 of 11
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
1.05 Client Side Connection Descriptions
Section Title
Connections
Column Title Function Legal Values
Port
Specify which port the device
is connected to the
FieldServer
P1-P8, R1-R2
1
Protocol Specify protocol used Gardner_Denver
Baud* Specify baud rate 1200, 9600 (match to Controller)
Parity* Specify parity
None
Data_Bits* Specify data bits
7
Stop_Bits* Specify stop bits
1
Handshaking*
Specify hardware
handshaking
None
Poll_Delay* Time between internal polls > = 0.2s
Timeout* Time to wait for response > = 0.6s
Example
// Client Side Connections
Connections
Port, Protocol
P1,
Gardner_Denv
er
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for
details of the ports available on specific hardware.