4.1.2. Driver Related Map Descriptor Parameters
Column
Title
Function Legal Values
Node_Name
Name of Node to fetch data
from
One of the node names specified
in “Client Node Descriptor” above
Gar_cmd Data poll commands
Service_Data, Operating_Mode,
Operating_Data
Gar_data
Data fields in a data poll
command response
message. Can be used to
poll for all or specific data
or just isolate specific items
in a “All” poll.
Available with Service_Data: All,
Advisories, Shutdown_codes,
Hourmeter_shutdown,
Hourmeter_total,
Hourmeter_loaded,
Hourmeter_temp,
Hourmeter_tmp_st, Last_maint_A,
Last_maint_B, Oilage
Available with Operating_Mode:
All, Oper_mode, Seq_number,
Oper_state
Available with Operating_Data: All,
System_pressure, Filter_pressure,
Discharge_temp, Reservoir_temp,
Motor_current
4.1.3. Timing Parameters
Column Title Function
Legal
Values
Scan_Interval
Rate at which data is polled. Note that the
Poll_Delay Connection parameter affects the
effective scan interval.
0.1s