IN addition to the ‘Everything’ keyword indicated in chapter 4 the following specific
query functions are implemented.
Func. Description Driver Parameter Protocol Id.
‘1’ DART Config Query DA_Func = dart-config 49
‘2’ Dart Psswd Query DA_Func = dart-password 50
'3' DAP Config Command DA_Func = dap-config 51
'4' DAP Log Query DA_Func = dap-log 52
'5' DAP Unit-Type Query DA_Func = dap-unit 53
'6' DAP Stat Query DA_Func = dap-stat 54
'7' DAP Xtra Query DA_Func = dap-xtra 55
'8' DAP Menu Query DA_Func = dap-menu 56
'A' Chiller Stat Query DA_Func = chiller-stat 65
'B' Chiller Xtra Query DA_Func = chiller-xtra 66
'C' Chiller Menu Query DA_Func = chiller-menu 67
‘D” Dart Status DA_Func = dart-status 68
'E' DAP80 Menu Query DA_Func = dap80-menu 69
'G' DAP Analog Query DA_Func = dap80-analog 71
'H' DAP Channels Query DA_Func = dap80_channles 72
Each of the above queries returns a complex set of data consisting of many sub-fields.
Contact Data-Aire for a complete listing of the data composite returned.
The following special / diagnostic functions are also implemented.
Driver Parameter Protocol Id.
DA_Func = All-Listen 11
DA_Func = Ack 6
DA_Func = Dart-Transparant 2
DA_Func = Dart-Opaque 3
DA_Func = Test-Echo 16
DA_Func = Test-No-Echo 15
DA_Func = Unit-Talk 13
With the exception of the Unit-Talk command, these are nodeless commands.
When using any of these special commands no other DA_* fields need be specified.
The operation of these functions is as follows ;
All-Listen instructs the all units in the network to switch their relays to the listen position.
Those units already in the listen position will do nothing. Those in the talk position will
first echo the all-listen command and then switch their relays to the listen position. A
pause of 0.15 seconds is required after the transmission of this command, to allow the
units time to switch their mechanical relays.
6.1.2 DA_Field Parameter - Permitted values.
Legal values depend on the value of DA_Func.