Page 6
4.2 Client Side Connections
Section Title
Connections
Column Title Function Legal Values
Port Specify which port the device is
connected to the FieldServer
This is the port connected to the
DART’s RS232 port.
P1-P8, R1-R2
(P1-P8) requires 232/485
converter.
Secondary_Port* Using a Dart ? Do not specify
this parameter.
P1-P8, R1-R2
(R1-R2) requires 232/485
converter.
Baud* Specify baud rate 2400 (Others available but
Daire only operates at 2400
baud.)
Parity* Specify parity
None
Data_Bits* Specify data bits
8
Stop_Bits* Specify stop bits
1
Protocol Specify protocol used
Either keyword may be used.
Dart
Handshaking* Specify hardware handshaking
None
Poll Delay* Time between internal polls 0-32000 seconds
default 1 second
Example
// Client Side Connections
Connections
Port, Parity, Data_Bits, Stop_Bits, Protocol, Poll_Delay
P1, 2400 , None, 8, 1, Dart , 0.100s