4.2 Client Side Connections
Section Title
Connections
Column Title Function Legal Values
Port Specify which port the device is
connected to the Bridge
P1-P8, R1-R2
Baud Specify baud rate
The driver supports all standard
baud rates 110 – 115200.
Gamewell panels only support a
baud rate of 2400.
2400
Parity* Specify parity
The driver supports the following
options. Even, Odd, None, Mark,
Space
The Gamewell panels only
support the use of no parity.
None
Data_Bits* Specify data bits
8
Stop_Bits* Specify stop bits
1
Protocol Specify protocol used Gamewell
Handshaking* Specify hardware handshaking
None
Poll _Delay* Time between internal polls 0-32000 seconds
default 1 second
IC_Timeout This driver does not use an inter
character timeout system. Failing
to set the IC_Timeout to zero will
result in driver errors.
0
Example
// Client Side Connections
Connections
Port, Baud, Parity, Protocol, Handshaking, Poll_Delay, IC_Timeout
P8, 9600, None, Gamewell, None , 0.100s , 0