FieldServer FS-8700-83 Computer Drive User Manual


 
FS-8700-83 Gamewell Page 5 of 24
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
4.3 Client Side Nodes
Section Title
Nodes
Column Title Function Legal Values
Node_Name Provide name for node Up to 32 alphanumeric
characters
Node_ID Gamewell panel node address.
The Node Id has no meaning
when the FieldServer is
connected directly to Gamewell
panel. When connecting to a
Gamewell panel directly always
set the Node_ID to zero. When
connecting to a Gamewell
SmartNet terminal. The
Node_ID is important and
should correspond to the
Node_ID’s of the panel’s
connected to the SmartNet
terminal.
0-256
Protocol Specify protocol used Gamewell
Port Specify which port the device is
connected to the FieldServer.
The use of R1 and R2 is only
appropriate when a 232/485
converter is used. The
Gamewell panels only have a
232 port available for
connection.
P1-P8, R1-R2
Example
// Client Side Nodes
Nodes
Node_Name, Node_ID, Protocol, Port
Panel1 , 0 , Gamewell, P8