Fujitsu M5000 Server User Manual


 
1-20 SPARC Enterprise M4000/M5000 Servers Overview Guide December 2010
1.3.6 Operator Panel
The operator panel (FIGURE 1-15), which is not redundant, displays the system status,
system problem alerts, and location of system faults. It also stores the system
identification anduser setting information.For more informationon the operatorpanel
functions, refer to the SPARC Enterprise M4000/M5000 Servers Service Manual.
TABLE 1-7 CPU Types and Maximum Power Consumption on the M4000 Server
*
* M4000 system configuration: CPUM x 2, MEMB x 4, 8GB DIMM x 32, HDD x 2, PCIe x 4, PCI-X x 1, DAT x 1.
CPU Type Frequency (GHz) Number
Power
Consumption (W)
Apparent
Power (VA) Heat Dissipation (KJ/h)
SPARC 64 VI processor 2.15 4 1556 1621 5602
SPARC 64 VII processor 2.4/2.53 4 1656 1725 5962
SPARC 64 VII+ processor 2.66 4 1692 1763 6091
TABLE 1-8 CPU Types and Maximum Power Consumption on the M5000 Server
*
* M5000 system configuration: CPUM x 4, MEMB x 8,8GB DIMM x 64, HDD x 4, PCIe x 8, PCI-X x 1, DAT x 1.
CPU Type Frequency (GHz) Number
Power
Consumption (W)
Apparent
Power (VA) Heat Dissipation (KJ/h)
SPARC 64 VI processor 2.15 8 2998 3123 10793
SPARC 64 VII processor 2.4/ 2.53 8 3198 3331 11513
SPARC 64 VII+ processor 2.66 8 3270 3406 11772