GE 600 - 1500 VA Power Supply User Manual


 
OPM_NPE_19X_600_1K5_2GB_V030 13 GE DE NetPro 19” 600-1500: User manual 3.0 (GB)
g
GE Digital Energy
NetPro 19” model : 600 1000 1500
Ratings
Voltage Amperes (VA) : 600 1000 1500
with computer type load
Watts (W) : 360 600 900
with resistive load
Input thermal circuit breaker (A) : 5 5 7
Input fuse (A) : 8 8 10
Input converter
AC input voltage : 220 - 240 V
AC input voltage range : 100% load: 187 - 264 V
70% load: 120 - 264 V
input >264 Vac: UPS switches to battery operation
input >312 Vac: UPS shuts down, manual restart required
Minimum start-up AC voltage : 187 V (at any load)
Input current waveform : sinusoidal
conform or better than EN 61000-3-2 (IEC 555-2)
Input current (A) at nom. inp. volt. : 2.0 3.3 5.0
Input power factor : 1
Input frequency range : 45 - 66 Hz
Inrush current : none
Output converter
AC output voltage : 230 V (suitable for 220 - 240 V loads)
AC output voltage tolerance : ± 2%
Output frequency : 50 or 60 Hz, front selectable
Output frequency range : nominal ± 0.15% unless synchronized to the mains
Output waveform : sine wave
Harmonic distortion : < 2% (typical 1.5%) with linear load
Power factor : 0.6 (0.7 at 90% load)
Crest factor (peak to RMS current) : suitable for loads with c.f. up to 6:1
Capacity appliance outlets : max. 10 A per outlet
Bypass
AC input voltage range : 195 - 264 V
Frequency tracking rate : 2 Hz/sec.
Frequency tracking range : nominal ± 10%
Phase difference : < 7º
Typical transfer time, msec : 4
Overload capability
: Fully protected against overload and short circuits
Overload behaviour (battery operation) : 110% during 5 minutes; 150% during 5 seconds
Overload behaviour during : depends on rating of thermal circuit breaker
bypass operation typical: 125% of TCB value for 200 seconds
200% of TCB value for 10 seconds
300% of TCB value for 4 seconds
Batteries (ratings given for 25ºC)
Nominal voltage (Vdc) : 24 36 48
Number of 7 Ah batteries : 2 3 4
Type : sealed lead acid, maintenance free
Service life : up to 6 years (depending on use)
Recharge current : 1.5 A
Battery recharge time
(batt. discharged at 100% load) : 1.5 hours for 90% capacity, std battery
Runtime in minutes
at typical load (75%) : 12 12 10
VA/Watts
100/60 : 64 104 124
200/120 : 34 54 71
400/240 : 15 27 36
600/360 : 9 15 24
1000/600 : - 9 12
1500/900 : - - 6
General
Weight without battery drawer (kg) : 14 14 14
Weight with battery drawer (kg) : 19 22 24
Dimensions (hxwxd, mm) : 133.5 (3HU) x 450 (19”) x 440
Depth required in 19” rack (mm) : 420 (without connectors)
Enclosure / protection : steel - plastic / IP20
Environment
Safety : EN 50091-1-1, EN 60950, IEC 950
Electromagnetic compatibility : EN 50091-2
Ambient temperature : -10 to +40ºC
Audible noise at 1 meter : < 45 dB(A), load and temperature dependent
Max. relative humidity : 95% (non-condensing)
8 - Specifications