GFK-2023C 3-1
Installation
Intelligence Panel PCs are designed for installation in switchboard panels and cabinet
doors. To facilitate installation and access to connectors, switchboard panels and
consoles must be accessible from the rear. The unit can be installed in switchgear
cubicles or cabinets with wall thicknesses of 2mm to 13mm (0.079 – 0.5 inches). For
optimum sealing with the cabinet face, the recommended wall thickness is
3mm (0.118 inches).
Air Inlets and outlets must have at least 25mm (approx. 1.0 inch) of space around them
and not be obstructed. Adequate airflow around the exterior of the unit is important to the
interior temperature of the unit. Two fans are used to create air flow through the industrial
computer to maintain a correct working temperature.
Caution
Only correct mounting ensures front-side NEMA and IP65 protection
Caution
The IC5005/BC5005 and IC5008/BC5008 units must be installed and
operated in a vertical position to ensure the correct operating
position of the CD-ROM drive.
Caution
Viewed from the front, there must be sufficient space (132 mm or
5.20 in. minimum) to the left of the units to allow the CD-ROM drive
drawer to open.
3
Chapter