HP (Hewlett-Packard) BL30p Server User Manual


 
Operating and
Performance
Specifications for
ProLiant BL p-Class
Power Enclosures
Single-Phase Model
3-Phase Model
Dimensions
Height
5.25 in (13.34 cm) 5.25 in (13.34 cm)
Width
27.15 in (68.96 cm) 27.15 in (68.96 cm)
Depth
17.60 in (44.7 cm) 17.60 in (44.7 cm)
Weights
No Hot-Plug
Power Supplies
47.5 lb (21.55 kg) 47.5 lb (21.55 kg)
All Hot-Plug
Power Supplies
99.5 lb (45.13 kg)
125.5 lb (56.93 kg)
Input Requirements
Rated input voltage
200 VAC to 240 VAC
200 VAC to 240 VAC line
to line
Rated input frequency
50 Hz to 60 Hz 50 Hz to 60 Hz
Rated input current
per side
24A
24A per phase
Rated input power
per side
5760 W 9976 W
Power cord
1 NEMA L6-30P per side
1 NEMA L15-30 per side
Output Voltage
Specifications
Rated output voltage
-48.8 VDC to -54 VDC -48.8 VDC to -54 VDC
Rated output current
99A
170A
Rated output power
4298 W 8310 W
Nominal power
4158 W at 208 VAC 7202 W at 208 VAC
Ambient Temperature
Range
(See
NOTE
)
Operating
50° to 95° F
(10° to 35° C)
50° to 95° F
(10° to 35° C)
Shipping
-22° to 140° F
(-30° to 60° C)
-22° to 140° F
(-30° to 60° C)
Relative humidity,
non-condensing
(See
NOTE
)
Operating
20% to 80% 20% to 80%
Non-operating
5% to 95% 5% to 95%
Wet Bulb
Temperature
Operating
82.4° F (28° C) 82.4° F (28° C)
Non-operating
101.7° F (38.7° C) 101.7° F (38.7° C)
NOTE:
Operating temperature has an altitude derating of 34° F (1° C) per 1,000 ft (304.8 m). No direct sunlight. Upper
operating limit is 10,000 ft (3,048 m) or 70Kpa/10.1 psia. Upper non-operating limit is 30,000 ft (9,144 m) or
30.3 KPa/4.4 psia. Storage maximum humidity of 95% is based on a maximum temperature of 113° F (45° C). Altitude
maximum for storage is 70 KPa.
QuickSpecs
HP ProLiant BL30p Server Blade
Technical Specifications
DA - 11958 North America — Version 6 — September 24, 2004
Page 36