HP (Hewlett-Packard) R1500 Power Supply User Manual


 
Specifications 33
Power protection specifications
UPS model VA
Nominal power rating
(W)
Nominal voltage setting
R1500 G2 NA 1440 1000 110, 120
R1500 G2 JPN/TWN 1200 900 100
1440 1000 110
R1500 G2 INTL 1500 1000 220, 230, 240
Voltage specifications
Configuration setting (VAC) Available nominal output voltage (VAC)
100 100
110 110
120 120
220 220
230 230
240 240
Output tolerance specifications
Source of power Regulation
Utility power (nominal
range)
-10% to +6% of nominal output voltage rating (within
the guidelines of the Computer Business Equipment
Manufacturers Association)
Battery power ±20% of nominal output voltage rating
Output feature specifications
Feature Specification
Online efficiency 95% nominal input voltage
Voltage wave shape Sine wave; 5% THD with typical PFC load
Surge suppression ANSI C62.41 Category A (formerly IEEE 587)
Noise filtering Full-time EMI/RFI filtering
Battery specifications
Feature Specification
Type
6 V, 9 AH, sealed, maintenance-free, valve-regulated,
rechargeable, lead-acid battery.
Voltage The battery modules have a battery string voltage of 36 V.
Charging
Advanced charging for faster recovery. Complete charge takes no
more than 24 hours. After approximately 4 hours, the batteries
reach 90% charge at default nominal utility voltage and no load.