HP (Hewlett-Packard) R5500 Power Supply User Manual


 
Installation 20
Connecting the REPO port
WARNING: The pins on the REPO port are polarity sensitive. Be sure to verify polarity while
connecting the REPO port.
WARNING: To meet the requirements stated in NEC (NFPA 70) Articles 645-10 and 645-11,
a UPS installed in a computer equipment room must be connected to a REPO circuit.
IMPORTANT: The remote switch must be in the Off (open) position to enable power to the
output receptacles.
NOTE: Wire the connector block using stranded, nonshielded wire (AWG #22 - #18, or
equivalent).