Hitachi L300P Power Supply User Manual


 
Using Intelligent Input Terminals
Operations
and Monitoring
4–34
Run Enable for
FW/RV (–xFU2
models only)
The Run Enable for FW/RV input provides a way to enable or disable the [FW] and [RV] input
terminals in real time, including a Run command from an operator keypad. This is useful for
applications that require a logic type safety interlock for FWD Run or REV Run commands.
The Run Enable for FW/RV function is assigned to an intelligent input terminal using option
code 49. When assigned, the output frequency operates as a logical AND of the Run Enable for
FW/RV input and a [FW], [RV], or keypad Run command input. The Run Enable for RV input
is level-sensitive, as shown in the timing diagram below. The leading edges (OFF-to-ON transi-
tions) of the Run Enable for RV input and the [FW] or [RV] input can occur in any order. The
output frequency follows the logical AND of these inputs.
Opt.
Code
Symbol Function Name
Input
State
Description
49 ROK Run Enable for
FW/RV
ON [FW] and [RV] inputs and operator Run
key press operate normally
OFF [FW] and [RV] inputs and operator Run
key press are ignored; inverter output
remains OFF
Valid for inputs:
C001, C002, C003, C004,
C005
Required
settings:
(none)
Notes:
This function is only available on –xFU2
models.
When the Run Enable for FW/RV function is
not assigned to any intelligent input terminal,
the FWD Run and REV Run commands
operate normally (directly control the output
frequency).
To ensure safe inverter operation in
networked applications, you cannot change an
intelligent terminal assignment to/from
[ROK] (option code 49) via the network.
However, you can still read an [ROK] input
assignment over the network.
[F/R] terminal
[ROK] terminal
Output
frequency
t
5 3 14 2
FW
TH
PLC
P24
CM1
See I/O specs on page 4–8.
ROK
Example (requires input configuration—
see page 3–43
):