Circuit Breaker
and Fuse Sizes
The inverter’s connections to input power must include UL Listed inverse time circuit breakers
with 600V rating, or UL Listed fuses as shown in the table below.
Wire Connectors
WARNING: Field wiring connections must
be made by a UL Listed and CSA Certified
ring lug terminal connector sized for the
wire gauge being used. The connector must
be fixed using the crimping tool specified by
the connector manufacturer.
Motor Overload
Protection
Hitachi L300P inverters provide solid state motor overload protection, which depends on the
proper setting of the following parameters:
B012 “electronic overload protection”
B212 “electronic overload protection, 2nd motor”
Set the rated current [Amperes] of the motor(s) with the above parameters. The setting range is
0.2 * rated current to 1.2 * rated current.
WARNING: When two or more motors are connected to the inverter, they cannot be protected
by the electronic overload protection. Install an external thermal relay on each motor.
Input
Volta ge
Motor
Output
200V
Inverter Models,
L300P
Circuit
Breaker
(A)
Fuse
(A)
Input
Volta ge
Motor
Output
400V
Inverter Models,
L300P
Circuit
Breaker
(A)
Fuse
(A)
HP kW HP kW
200V
2 1.5 -015LFU2 10 10
400V
2 1.5 -015HFU2, HFE2 10 10
3 2.2 -022LFU2 15 15 3 2.2 -022HFU2, HFE2 10 10
5 3.7 -037LFU2 20 20 5 4.0 -040HFU2, HFE2 15 15
7.5 5.5 -055LFU2 30 30 7.5 5.5 -055HFU2, HFE2 15 15
10 7.5 -075LFU2 40 40 10 7.5 -075HFU2, HFE2 20 20
15 11 -110LFU2 60 60 15 11 -110HFU2, HFE2 30 30
20 15 -150LFU2 70 70 20 15 -150HFU2, HFE2 35 35
25 18.5 -185LFU2 90 90 25 18.5 -185HFU2, HFE2 50 50
30 22 -220LFU2 100 100 30 22 -220HFU2, HFE2 50 50
40 30 -300LFU2 150 150 40 30 -300HFU2, HFE2 70 70
50 37 -370LFU2 175 175 50 37 -370HFU2, HFE2 80 80
60 45 -450LFU2 200 200 60 45 -450HFU2, HFE2 100 100
75 55 -550LFU2 250 250 75 55 -550HFU2, HFE2 125 125
100 75 -750LFU2 300 300 100 75 -750HFU2, HFE2 150 150
125 90 -900HFU2, HFE2 200
150 110 -1100HFU2, HFE2 225
175 132 -1320HFU2, HFE2 300
Terminal (ring lug)
Cable support
Cable