Hitachi L300P Power Supply User Manual


 
L300P Inverter
Configuring Drive
Parameters
3–57
“P” Group: Expansion Card Functions
The two (optional) expansion cards for the L300P have associated configuration data. The
following table defines the functions and their value ranges. Please refer to the expansion card
manual for more details.
NOTE: Parameters P044 to P049 are available only in inverters with manufacturing code
x8K xxxxxx xxxxx or later. The manufacturing code is printed on the product specifications
labels, located on the front and side of the inverter housing.
“P” Function
Run
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name Description
–FE2
(CE)
–FU2
(UL)
–FR
(Jpn)
P001 Operation mode on
expansion card 1 error
Two option codes:
00 Trip (stop motor)
01 Continuous operation
✘ ✔ 00 00 00
>P001 OPTION1
SELECT TRP
P002 Operation mode on
expansion card 2 error
Two option codes:
00 Trip (stop motor)
01 Continuous operation
✘ ✔ 00 00 00
>P002 OPTION2
SELECT TRP
P031 Accel/decel time input
selection
Three options:
00 Inverter
01 Expansion card 1
02 Expansion card 2
✘ ✘ 00 00 00
>P031 ACC/DEC
SELECT REM
P044 DeviceNet comm
watchdog timer
Range is 0.00 99.99 seconds ✘ ✘ 1.00 1.00 1.00
>P044 DEVICENET
TIMER 01.00s
P045 Inverter action on
DeviceNet comm error
Five options:
00 Trip
01 Decelerate and trip
02 Hold last speed
03 Free run stop
04 Decelerate and stop
✘ ✘ 01 01 01
>P045 DEVICENET
T-OUT FTP
P046 DeviceNet polled I/O:
Output instance number
Three settings:
20, 21, 100
✘ ✘ 21 21 21
>P046 DEVICENET
O-AS-INS 021
P047 DeviceNet polled I/O:
Input instance number
Three settings:
70, 71, 101
✘ ✘ 71 71 71
>P047 DEVICENET
O-AS-INS 071
P048 Inverter action on
DeviceNet idle mode
Five options:
00 Trip
01 Decelerate and trip
02 Hold last speed
03 Free run stop
04 Decelerate and stop
✘ ✘ 01 01 01
>P048 DEVICENET
IDLE FTP
P049 DeviceNet motor poles
setting for RPM
Range is 0 to 38 (even
numbers only)
✘ ✘ 000poles
>P049 DEVICENET
P 00P