“A” Group: Standard Functions
Configuring Drive
Parameters
3–24
NOTE: For A095 and A096 (and for 2nd motor settings), if you set a very rapid Acc1 or Dec1
time (less than 1.0 second), the inverter may not be able to change rates to Acc2 or Dec2 before
reaching the target frequency. In that case, the inverter decreases the rate of Acc1 or Dec1 in
order to achieve the second ramp to the target frequency.
A096 Dec1 to Dec2 frequency
transition point
Output frequency at which
Decel1 switches to Decel2,
range is 0.00 to 400.0 Hz
✘ ✘ 0.0 0.0 0.0 Hz
>A096 DECEL
CHFr 0000.00Hz
A296 Dec1 to Dec2 frequency
transition point, 2nd
motor
Output frequency at which
Decel1 switches to Decel2,
range is 0.00 to 400.0 Hz
(2nd motor)
✘ ✘ 0.0 0.0 0.0 Hz
>A296 2DECEL