Hitachi L300P Power Supply User Manual


 
L300P Inverter
Configuring Drive
Parameters
3–23
Second
Acceleration and
Deceleration
Functions
The L300P inverter features two-stage acceleration and deceleration ramps. This gives flexibil-
ity in the profile shape. You can specify the frequency transition point, the point at which the
standard acceleration (F002) or deceleration (F003) changes to the second acceleration (A092)
or deceleration (A093). These profile options are also available for the second motor settings
and third motor settings. All acceleration and deceleration times are time to ramp from zero
speed to full speed or full speed to zero speed. Select a transition method via A094 as depicted
below. Be careful not to confuse the second acceleration/deceleration settings with settings for
the second motor!
.
Accel 1
0
Accel 2
frequency
1
0
2CH
input
frequency
Accel 1
Accel 2
Frequency
transition point
A095
A094=00 A094=01
t
t
“A” Function
Run
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name Description
–FE2
(CE)
–FU2
(UL)
–FR
(Jpn)
A092 Acceleration (2) time
setting
Duration of 2nd segment of
acceleration, range is:
0.01 to 3600 sec.
✔ ✔ 15.015.015.0 sec.
>A092 ACCEL
TIME2 0015.00s
A292 Acceleration (2) time
setting, 2nd motor
Duration of 2nd segment of
acceleration, 2nd motor,
range is: 0.01 to 3600 sec.
✔ ✔ 15.015.015.0 sec.
>A292 2ACCEL
TIME2 0015.00s
A093 Deceleration (2) time
setting
Duration of 2nd segment of
deceleration, range is:
0.01 to 3600 sec.
✔ ✔ 15.015.015.0 sec.
>A093 DECEL
TIME2 0015.00s
A293 Deceleration (2) time
setting, 2nd motor
Duration of 2nd segment of
deceleration, 2nd motor,
range is: 0.01 to 3600 sec.
✔ ✔ 15.015.015.0 sec.
>A293 2DECEL
TIME2 0015.00s
A094 Select method to switch
to Acc2/Dec2 profile
Two options for switching
from 1st to 2nd accel/decel:
00 2CH input from terminal
01 transition frequency
✘ ✘ 00 00 00
>A094 ACCEL
CHANGE TM
A294 Select method to switch
to Acc2/Dec2 profile,
2nd motor
Two options for switching
from1st to 2nd accel/decel:
00 2CH input from terminal
01 transition frequency (2nd
motor)
✘ ✘ 00 00 00
>A294 ACCEL
CHANGE TM
A095 Acc1 to Acc2 frequency
transition point
Output frequency at which
Accel1 switches to Accel2,
range is 0.00 to 400.0 Hz
✘ ✘ 0.0 0.0 0.0 Hz
>A095 ACCEL
CHFr 0000.00Hz
A295 Acc1 to Acc2 frequency
transition point, 2nd
motor
Output frequency at which
Accel1 switches to Accel2,
range is 0.00 to 400.0 Hz
(2nd motor)
✘ ✘ 0.0 0.0 0.0 Hz
>A295 2ACCEL
CHFr 0000.00Hz