Hitachi L300P Power Supply User Manual


 
“B” Group: Fine-Tuning Functions
Configuring Drive
Parameters
3–42
Free-setting
V/f Pattern
The free-setting V/f inverter mode of operation uses voltage and frequency parameter pairs to
define seven points on a V/f graph. This provides a way to define a multi-segment V/f curve
that best suits your application.
The frequency settings do require that F1 F2 F3 F4 F5 F6 F7; their values must have
this ascending order relationship. To satisfy this criterion during initial parameter editing, set
F7 (B012) and work backwards when setting these values, since the defaults are all 0 Hz.
However, the voltages V1 to V7 may either increase or decrease from one to the next. There-
fore, you may set these parameters in any order.
“B” Function
Run
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name Description
–FE2
(CE)
–FU2
(UL)
–FR
(Jpn)
B100 Free-setting V/f
frequency (1)
V/f point 1, frequency
coordinate
✘ ✘ 0. 0. 0. Hz
>b101 FREE-V/F
V1 000.0V
B101 Free-setting V/f
voltage (1)
V.F point 1, voltage coordi-
nate
✘ ✘ 0.0 0.0 0.0 V
>b102 FREE-V/F
F1 0000Hz
B102 Free-setting V/f
frequency (2)
V/f point 2, frequency
coordinate
✘ ✘ 0. 0. 0. Hz
>b103 FREE-V/F
V2 000.0V
B103 Free-setting V/f
voltage (2)
V.F point 2, voltage coordi-
nate
✘ ✘ 0.0 0.0 0.0 V
>b104 FREE-V/F
F2 0000Hz
B104 Free-setting V/f
frequency (3)
V/f point 3, frequency
coordinate
✘ ✘ 0. 0. 0. Hz
>b105 FREE-V/F
V3 000.0V
B105 Free-setting V/f
voltage (3)
V.F point 3, voltage coordi-
nate
✘ ✘ 0.0 0.0 0.0 V
>b106 FREE-V/F
F3 0000Hz
B106 Free-setting V/f
frequency (4)
V/f point 4, frequency
coordinate
✘ ✘ 0. 0. 0. Hz
>b107 FREE-V/F
V4 000.0V
B107 Free-setting V/f
voltage (4)
V.F point 4, voltage coordi-
nate
✘ ✘ 0.0 0.0 0.0 V
>b108 FREE-V/F
F4 0000Hz
B108 Free-setting V/f
frequency (5)
V/f point 5, frequency
coordinate
✘ ✘ 0. 0. 0. Hz
>b109 FREE-V/F
V5 000.0V
B109 Free-setting V/f
voltage (5)
V.F point 5, voltage coordi-
nate
✘ ✘ 0.0 0.0 0.0 V
>b110 FREE-V/F
F5 0000Hz
B110 Free-setting V/f
frequency (6)
V/f point 6, frequency
coordinate
✘ ✘ 0. 0. 0. Hz
>b111 FREE-V/F
V6 000.0V
B111 Free-setting V/f
voltage (6)
V.F point 6, voltage coordi-
nate
✘ ✘ 0.0 0.0 0.0 V
>b112 FREE-V/F
F6 0000Hz
B112 Free-setting V/f
frequency (7)
V/f point 7, frequency
coordinate
✘ ✘ 0. 0. 0. Hz
>b113 FREE-V/F
V7 000.0V
B113 Free-setting V/f
voltage (7)
V.F point 7, voltage coordi-
nate
✘ ✘ 0.0 0.0 0.0 V
>b114 FREE-V/F
F7 0000Hz