Hitachi L300P Power Supply User Manual


 
L300P Inverter
Configuring Drive
Parameters
3–55
Miscellaneous
Functions
The following table contains miscellaneous functions not in other function groups.
C102/C103: Reset Mode / Restart Mode – The reset mode selection, set via parameter C102,
determines how the inverter responds to the [RS] intelligent input signal or keypad Stop/Reset
key in a trip condition. The options allow you to cancel the trip on either the OFF-to-ON or
ON-to-OFF transition of [RS], and if desired, stop the inverter if it is in Run Mode. A trip event
causes the inverter output to the motor to turn OFF immediately. If in Run Mode when the trip
occurred, the inverter and motor will enter free-run stop (coasting) operation. In some applica-
tions, the motor and load will still be coasting when the inverter returns to normal Run Mode
operation. For that situation, you can configure the inverter output (C103=00) to resume opera-
tion from 0 Hz and accelerate normally. Or, you can configure the inverter (C103=01) to
resume operation from the current speed of the motor (frequency matching)—often used in
applications such as HVAC.
“C” Function
Run
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name Description
–FE2
(CE)
–FU2
(UL)
–FR
(Jpn)
C091 Debug mode enable Two option codes:
00 Display
01 No display
✘ ✔ 00 00 00
>C091 INITIAL
DEBG OFF
C101 Up/Down memory
mode selection
Controls speed setpoint for
the inverter after power
cycle. Two option codes:
00 Clear last frequency
(return to default
frequency F001)
01 Keep last frequency
adjusted by UP/DWN
✘ ✔ 00 00 00
>C101 UP/DWN
DATA NO-STR
“C” Function
Run
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name Description
–FE2
(CE)
–FU2
(UL)
–FR
(Jpn)
C102 Reset mode selection Determines response to
Reset input [RS].
Three option codes:
00 Cancel trip state at input
signal ON transition,
Stops inverter if in Run
Mode
01 Cancel trip state at signal
OFF transition, Stops
inverter if in Run Mode
02 Cancel trip state at input
signal ON transition, no
effect if in Run Mode
✔ ✔ 00 00 00
>C102 RESET
SELECT ON
C103 Restart mode after reset Two option codes:
00 Restart at 0 Hz
01 Resume operation after
frequency matching
✘ ✔ 00 00 00
>C103 RESET
f-Mode ZST