Hitachi L300P Power Supply User Manual


 
L300P Inverter
Configuring Drive
Parameters
3–43
“C” Group: Intelligent Terminal Functions
The five input terminals [1], [2], [3], [4], and [5] can be configured for any of 33 different
functions (34 functions for –xFE2/–xFU2 models). The next two tables show how to configure
the five terminals. The inputs are logical, in that they are either OFF or ON. We define these
states as OFF=0, and ON=1.
The inverter comes with default options for the five terminals. These default settings are
initially unique, each one having its own setting. Note that European and US versions have
different default settings. You can use any option on any terminal.
Input Terminal
Configuration
Functions and Options – The function codes in the following table let you assign one of 33
(or 34) options to any of the five logic inputs for the L300P inverters. The functions C001
through C005 configure the terminals [1] through [5] respectively. The “value” of these partic-
ular parameters is not a scalar value, but it is a discrete number that selects one option from
many available options.
For example, if you set function C001=01, you have assigned option 01 (Reverse Run) to
terminal [1]. The option codes and the specifics of how each one works are in Chapter 4.
“C” Function
Run
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name Description
–FE2
(CE)
–FU2
(UL)
–FR
(Jpn)
C001 Terminal [1] function
33 programmable
functions
(34 functions for
–xFE2/–xFU2
models) available for
terminals (see next
section)
✘ ✔ 18
[RS]
18
[RS]
18
[RS]
>C001 IN-TM
1 RS
C002 Terminal [2] function ✘ ✔ 16
[AT]
16
[AT]
16
[AT]
>C002 IN-TM
2 AT
C003 Terminal [3] function ✘ ✔ 03
[CF2]
13
[USP]
03
[CF2]
>C003 IN-TM
3 JG
C004 Terminal [4] function ✘ ✔ 02
[CF1]
02
[CF1]
02
[CF1]
>C004 IN-TM
4 FRS
C005 Terminal [5] function ✘ ✔ 01
[RV]
01
[RV]
01
[RV]
>C005 IN-TM
5 2CH