Hitachi L300P Power Supply User Manual


 
L300P Inverter
Configuring Drive
Parameters
3–39
“B” Function
Run
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name Description
–FE2
(CE)
–FU2
(UL)
–FR
(Jpn)
B080 [AM] terminal analog
meter adjustment
Adjust 8-bit gain to analog
meter connected to terminal
[AM], range is 0 to 255
✔ ✔ 180 180 180
>b080 AM-MONITOR
ADJUST 180
B081 [FM] terminal analog
meter adjustment
Adjust 8-bit gain to analog
meter connected to terminal
[FM], range is 0 to 255
✔ ✔ 60 60 60
>b081 FM-MONITOR
ADJUST 060
B082 Start frequency adjust-
ment
Sets the starting frequency
for the inverter output, range
is 0.10 to 9.99 Hz
✘ ✔ 0.50 0.50 0.50 Hz
>b082 fmin
F 00.50Hz
B083 Carrier frequency
setting
Sets the PWM carrier (inter-
nal switching frequency).
Range is 0.5 to 8.0 kHz for
–015xxx to –750xxx models
and 0.5 to 12.0 kHz for
–900Hxx to 1320Hxx
✘ ✔ 3.0 3.0 3.0 kHz
>b083 CARRIER
F 05.0kHz
B084 Initialization mode
(parameters or trip
history)
Select the type of initializa-
tion to occur, two option
codes:
00 Trip history clear
01 Parameter initialization
02 Trip history clear and
parameter initialization
✘ ✘ 00 00 00
>b084 INITIAL
MODE TRP
B085 Country code for initial-
ization
Select default parameter
values for country on initial-
ization, four option codes:
00 Japan version
01 Europe version
02 US version
03 reserved (do not set)
✘ ✘ 01 02 00
>b085 INITIAL
SELECT USA
B86 Frequency scaling
conversion factor
Specify a constant to scale
D007 to display in engineer-
ing units.
Range is 0.1 to 99.9
✔ ✔ 1.0 1.0 1.0
>b086 F-CONV
Gain 001.0
B087 STOP key enable Select whether the STOP
key on the keypad is enabled
(req. A002=01, 03, 04, or
05). Two option codes:
00 Enable
01 Disable
✘ ✔ 00 00 00
>b087 STOP-SW
SELECT ON