Input
Voltag e
Motor
Output
400V
Inverter
Models,
L300P
Length
of
power
wiring
Screw size
of terminal
Ring Lug Connector *1 Torque
HP kW (AWG–bolt)
(mm
2
–bolt)
ft-lbs N-m
400V
2 1.5 –015HFU2, HFE2 M4 14–10 2–4 1.1 1.5
3 2.2 –022HFU2, HFE2 M4 14–10 2–4 1.1 1.5
5 4.0 –040HFU2, HFE2 M4 14–10 2–4 1.1 1.5
7.5 5.5 –050HFU2, HFE2 M5 14–12 2–5 1.8 2.5
10 7.5 –075HFU2, HFE2 M5 10–12 3.5–5 1.8 2.5
15 11 -110HFU2, HFE2 M6 8–1/4 5.5–6 3.6 4.9
20 15 -150HFU2, HFE2 M6 6–1/4 8–6 3.6 4.9
25 18.5 -185HFU2, HFE2 M6 6–1/4 14–6 3.6 4.9
30 22 -220HFU2, HFE2 M6 4–1/4 14–6 3.6 4.9
40 30 -300HFU2, HFE2 M6 3–1/4 22–6 3.6 4.9
50 37 -370HFU2, HFE2 M6 4–1/4 14–6 3.6 4.9
60 45 -450HFU2, HFE2 M8 1–5/16 38–8 6.5 8.8
75 55 -550HFU2, HFE2 M8 3–5/16 22–8 6.5 8.8
100 75 -750HFU2, HFE2 M8 2–5/16 30–8 6.5 8.8
125 90 -900HFU2, HFE2 M10 1–1/2 38–10 10.1 13.7
150 110 -1100HFU2, HFE2 M10 1/0–1/2 50–10 10.1 13.7
175 132 -1320HFU2, HFE2 M10 2/0–1/2 60–10 10.1 13.7