Hitachi L300P Power Supply User Manual


 
Step-by-Step Basic Installation
Inverter Mounting
and Installation
2–16
Terminal
Dimensions and
Torque Specs
The following tables list the screw size of terminal and recommended torque for tightening for
each of the L300P inverter models (400V models are on the next page).
CAUTION: Fasten the screws with the specified fastening torque in the table below. Check for
any loosening of screws. Otherwise, there is the danger of fire.
Note 1: The recommended ring lug connector listing consists of wire size – screw size
format. The wire sizes are in AWG or mm
2
format. For AWG wire sizes, bolt sizes
for the ring lug centers are: #10, #12, 1/4”, 5/16”, and 1/2”. For metric wire sizes, bolt
sizes for the ring lug centers are: 6 = 6M, 8 = 8M, 10 = 10M
TIP: AWG = American Wire Gauge. Smaller numbers represent increasing wire thickness.
kcmil = 1,000 circular mils, a measure of wire cross-sectional area
mm
2
= square millimeters, a measure of wire cross-sectional area
Input
Voltage
Motor
Output
200V
Inverter
Models,
L300P
Length
of
power
wiring
Screw size
of terminal
Ring Lug Connector *1 Torque
HP kW (AWG–bolt)
(mm
2
–bolt)
ft-lbs N-m
200V
2 1.5 –015LFU2 M4 14–#10 2–4 1.1 1.5
3 2.2 –022LFU2 M4 14–#10 2–4 1.1 1.5
5 3.7 –037LFU2 M4 10–#10 3.5–4 1.1 1.5
7.5 5.5 –055LFU2 M5 8–#12 5.5–5 1.8 2.5
10 7.5 –075LFU2 M5 8–#12 8–5 1.8 2.5
15 11 -110LFU2 M6 4–1/4 14–6 3.6 4.9
20 15 -150LFU2 10m M6 2–1/4 22–6 3.6 4.9
< 10m 4–1/4 14–6
25 18.5 -185LFU2 M6 4–1/4 14–6 3.6 4.9
30 22 -220LFU2 M8 1–5/16 38–8 6.5 8.8
40 30 -300LFU2 10m M8 2–5/16 22–8 6.5 8.8
< 10m 2–5/16 30–8
50 37 -370LFU2 10m M8 2–5/16 30–8 6.5 8.8
< 10m 1–5/16 38–8
60 45 -450LFU2 M10 1–1/2 38–10 10.1 13.7
75 55 -550LFU2 10m M10 2/0–1/2 60–10 10.1 13.7
< 10m 3/0–1/2 80–10
100 75 -750LFU2 10m M10 3/0–1/2 80–10 10.1 13.7
< 10m 250kcmil–1/2 125–10