Honeywell PRO-2200 Power Supply User Manual


 
14 PRO-2200 Power Supply With Battery Backup PRO22E1PS
Installation Guide
Cable Specifications
Application NCI Part No. AWG Description Max. Dist. Imp. Cap.
N-485 connections NC2442-TN N/A Belden 9842 4000' (1200 m) 12012.8pf/ft
N/A or equivalent
CR-1, TR-1, CI-1, KR-1 NC1861-BL 18 6 conductor shielded 500' (152 m)
Wiegand card readers
NR-1 magstripe reader NC1861-BL 18 6 conductor shielded 500' (152 m)
PR-1-280 Cotag reader:
280 read head to SZC NC1861-BL 18 6 conductor shielded 300' (91 m)
SZC to N-1000-II NC1861-BL 18 6 conductor shielded 500' (152 m)
PR-2 Hughes reader:
scanner to reader NC1861-BL 18 6 conductor shielded 30' (9 m)
reader to N-1000-II NC1861-BL 18 6 conductor shielded 500' (152 m)
PR-3, PR-5 Indala readers:
A-3/A-5 read head to RE-2 NC18121-YL 18 12 conductor shielded 75' (23 m)
RE-2 to N-1000-II NC1861-BL 18 6 conductor shielded 500' (152 m)
PR-20 , PR-22 Indala readers:
A-20/A-22 read head
to RE-2 NC18121-YL 18 12 conductor shielded 75' (23 m)
RE-2 to N-1000-II NC1861-BL 18 6 conductor shielded 500' (152 m)
PR-10, PR-12 Indala readers: NC1861-BL 18 6 conductor shielded 500' (152 m)
HG-3 hand geometry reader: NC1861-BL 18 6 conductor shielded 500' (152 m)
5 conductor keypad NC1861-BL 18 6 conductor shielded 500' (152 m)
Alarm input points NC 2221-BR 22 2000' (610 m)
Relay outputs NC 1821-OR 18 twisted pair, shielded 2000' (610 m)
NOTE:
For Plenum rated cable just add a “P” to Northern’s part number prefix; for example NC1861-BL
becomes PNC1861-BL