IBM 42X Personal Computer User Manual


 
NetBAY Power Distribution Units 179
Rack PDU specifications
When connected to a dedicated power source, the Rack PDU conforms to UL950, CSA
22.0-950, EN-60950, and IEC-950 standards. The following table contains the product
specifications for the Rack PDU:
Height 43 mm (1.7 in.)
Width 192 mm (7.5 in.)
Depth 221 mm (8.7 in.)
Weight 2.4 kg (5.4 lbs)
Operating temperatures 10°C35°C (50°F95°F) at 0914 m (03000 ft)
10°C32 °C (50°F90°F°) at 9142133 m (30007000 ft)
Operating humidity 880% (non-condensing)
Rated voltage 100127 V ac, 15 A, single-phase
200-240 V ac, 10 A, single-phase
Rated frequency 5060 Hz
Maximum power rating 2400 VA
Power inlet Two IEC 320-C20 inlets rated at 16 A (VDE) / 20 A (UL/CSA)
Transfer time <35 ms from main to backup power
Power outlets Four IEC 320-C13 outlets rated at 10 A (VDE) / 15 A
(UL/CSA)