ICP DAS USA 8830 Network Card User Manual


 
#AASi
Command
#AASi
Description
Reads the analog input or counter/frequency module data for all
channels from specified slot in the I-8000 unit.
#AASi[CHK](cr)
# A delimiter character
AA A 2-character HEX module address for the
specified I-8000 system ,ranging from 01 to FFh
Si The specified slot number. i = 0 to 3 (4 slots) or
i = 0 to 7 (8 slots)
[CHK] 2-characters of checksum
Syntax
(cr) Character Return(0x0D) for denote the end of
command
Valid Command >(data)[chk](cr)
Invalid Command ?AA[CHK](cr)
Syntax error or communication error may get no response.
> A delimiter for valid command
? A delimiter for invalid command
AA A 2-character HEX module address
(data) A return string from the RTD input module in
engineering mode.
[CHK] A 2-character checksum
(cr) Carriage Return(0x0D) to denote the end of
response
Command
#01S3
Response
>+2.1234+2.1234 +2.1234 +2.1234 (cr)
Example
Description The data read from analog data input module
i-87013 (4 channels analog input module) in slot 3
of the I-8000 system at address 01h is
+2.1234+2.1234 +2.1234 +2.1234.
Note: i-87013 Î 4-Channel RTD Analog Input Module
i-8017H Î Fast 8-Channel mV/V/mA Analog Input Module
i-87017 Î 8-Channel mV/V/mA Analog Input Module
i-87018 Î 8-Channel mV/V/mA and Thermocouple Analog Input
Module
i-8080 Î 8-Channel Counter/Frequency Module
8430/8830/8KE4/8KE8 User’s manual, Jan 2005, Version 1.0, 8MS-002-10 ----- 72