# AASi00(data) For multiple channels DO output
Command
#AASi00(data)
Description
Sends the value to the digital output module for multiple channels output of
a specified slot in the I-8000 unit
#AASi00(data)[CHK](cr)
$ A delimiter character
AA A 2-character HEX module address for the specified
I-8000 unit ,ranging from 01 to FFh
Si The specified slot number. i = 0 to 3(4 slots) or
i = 0 to 7(8 slots)
00 00 that for multiple channels’ DO output
(data) A 2-character or 4-character HEX for digital output
value.
For output from all channels, the data will be
2-character HEX for channel count is less than or
equal to 8 bits, 4-character for channel count is 16 bits
and greater than 8 bits. The data bit is corresponds to
the output module channel.
[CHK] 2-characters of Checksum
Syntax
(cr) Carriage Return (0x0D) to denote the end of the
command
Valid Command >[chk](cr)
Invalid Command ?AA[CHK](cr)
Any syntax or communication error may receive no response.
> A delimiter for valid command
? A delimiter for invalid command
[CHK] A 2-character of checksum
(cr) Carriage Return (0x0D) to denote the end of the
response
Note If any channel of digital output module (*1) is configured for an analog
input alarms then this command has no effect on the specified channel.
The channel is always used for analog input alarms and can not be
configured again unless it is disconnected.
Refer to:
Analog Input Alarm
(*1) For digital output modules not support analog input alarm are :
i-8041, i-87041, i-87042, i-8050
Command
#01S30042
Response
>(cr)
Description This example is for an 8-channel digital output
module. The Digital output Module in slot 3 and
channel 2 and channel 6 of the I-8000 unit at address
01h will be set to ON. This example is only for output
modules where the channel number is less than or
equal to 8.
Command
#01S300AA55(cr)
Response
>(cr)
Example
Description